PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
102
05
Cold restart not possible:
OVERALL RESET required
102
06
Power failure: OVERALL
RESET required
102
07
I/O module unclear:
OVERALL RESET required
102
08
Cenral bus wrongly
terminated:
Component structure error
102
09
Block address list structure
not completed:
OVERALL RESET required
Additional info 1:
Address 1, undefined
character
B-58
Possible Cause
Error group No. 18
NINEU bit set:
-
NAU routine has interrupted
operating system function
Error group No. 18
NAU signal active:
-
NAU routine has interrupted
operating system function
NINEU bit not set
Error group No. 19
PEU signal active:
-
Power failure in expansion unit
-
Connection with expansion unit
interrupted
-
Central controller connector is
missing
-
Wrong IM304 jumper assignment
Error group No. 19
-
ASF signal active (I/O)
Error group No. 17
Operating system function
interrupted
S5-115F Manual
Remedy
Warm restart:
-
OVERALL RESET
Warm restart:
-
OVERALL RESET
-
Check power supply in
expansion unit
-
Check connection
-
Plug terminating resistor into
central controller
-
Check jumpers
Warm restart:
-
OVERALL RESET
-
Check bus connections
Warm restart:
-
OVERALL RESET
Warm restart:
-
OVERALL RESET
EWA 4NEB 811 6149-02