Siemens SIMATIC S5 Manual page 309

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
56
01
I/O modules cannot be
accessed:
I/O module or IM error
Additional info. 1:
I/O word No.
58
01
59
PL cannot be accessed:
60
PL or CPU HW error
61
62
63
Additional info. 1:
No. before processed program
Additional info. 2:
Data pointer
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 19
QVZ during access of the I/O module
(short test):
-
Module defective
-
Wrong address on the IM306
-
IM306 defective
Word address at which the QVZ was
detected,
decimal display
Error group No. 01
QVZ during access of PL:
-
PL defective
-
CPU HW error
PLC Error Messages
Remedy
-
Replace module
-
Check addressing
-
Replace IM306
Warm restart:
1. Stop/Run
-
Replace PL
-
Replace CPU
Warm restart:
1. POWER OFF/ON
2. Stop/Run
B-49