PLC Error Messages
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
16
04
Long discrepancy time for
current DI bit not found:
Configuration/CPU error
Additional info. 1:
DI byte No.
Additional info. 2:
DI bit No.
16
05
QVZ during DI access:
I/O module error
Additional info. 1:
DI word No.
B-6
Possible Cause
Error group No. 13
-
Configuration:
*
Long discrepancy time in
discrep. DB not configured
*
Discrepancy DB not present
in PLC
-
CPU error
Byte address of the current DI bits,
decimal display
Bit No. of the current DI bits,
decimal display
Error group No. 19
-
DI module defective
-
IM306 defective
-
IM304/314 defective
Address of the accessed DI module
S5-115F Manual
Remedy
-
Check configuration
-
Replace CPU
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace module
-
Replace module
-
Replace module
Warm restart:
1. Stop/Run
EWA 4NEB 811 6149-02