Siemens SINAMICS G130 Engineering Manual page 425

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Rated power at
Active Line Modules (incl. Active Interface Modules)
400 V
Order No.
[kW]
Supply voltage 380 V – 480 V 3AC (DC Link Voltage 570 V – 720 V)
132
6SL3730-7TE32-1BA3
160
6SL3730-7TE32-6BA3
235
6SL3730-7TE33-8BA3
300
6SL3730-7TE35-0BA3
380
6SL3730-7TE36-1BA3
500
6SL3730-7TE38-4BA3
630
6SL3730-7TE41-0BA3
630
6SL3730-7TE41-0BC3
900
6SL3730-7TE41-4BA3
900
6SL3730-7TE41-4BC3
Rated power at
500 V / 690 V
[kW]
Supply voltage 500 V – 690 V 3AC (DC Link Voltage 750 V – 1035 V)
400 / 630
6SL3730-7TG35-8BA3
580 / 800
6SL3730-7TG37-4BA3
580 / 800
6SL3730-7TG37-4BC3
800 / 1100
6SL3730-7TG41-0BA3
800 / 1100
6SL3730-7TG41-0BC3
1015 / 1400
6SL3730-7TG41-3BA3
1015 / 1400
6SL3730-7TG41-3BC3
Order numbers of the various air-cooled Active Line Modules with associated Active Interface Modules
Please note that parallel connections can only be made with Active Line Modules and the associated Active Interface
modules of exactly the same power rating. The potential for imbalances in current distribution means that current
derating of 5 % must be applied and this must be taken into account when the Modules are dimensioned.
Please also refer to the instructions regarding parallel connections in chapter "Fundamental Principles and System
Description", as well as to the guidance relating to the use of DRIVE-CLiQ cables and their installation in section
"Information about equipment handling / DRIVE-CLiQ wiring".
SINAMICS S120 Cabinet Modules
For parallel connection, mounted on left of LCM
(mirrored mounting)
For parallel connection, mounted on left of LCM
(mirrored mounting)
For parallel connection, mounted on left of LCM
(mirrored mounting)
For parallel connection, mounted on left of LCM
(mirrored mounting)
For parallel connection, mounted on left of LCM
(mirrored mounting)
SINAMICS Engineering Manual – November 2015
Engineering Information
425/528
Ó Siemens AG

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s150

Table of Contents