2
The factory settings for current controller clock cycle and pulse frequency are 250 μs and 2.00 kHz respectively for the
SINAMICS G and S converters below. Their maximum settable pulse frequency is 8.0 kHz:
- 380 V – 480 V 3AC: ≤ 250 kW / 490 A or 510 V – 720 V DC: ≤ 250 kW / 490 A
3
The factory settings for current controller clock cycle and pulse frequency are 400 μs and 1.25 kHz respectively for the
SINAMICS G and S converters below. Their maximum settable pulse frequency is 7.5 kHz:
- 380 V – 480 V 3AC: ≥ 315 kW / 605 A or 510 V – 720 V DC: ≥ 315 kW / 605 A
- 500 V – 600 V 3AC: All power ratings or
- 660 V – 690 V 3AC: All power ratings or
In the vector-type drive object with vector control mode settable pulse frequencies and associated maximum attainable
output frequencies as a function of the current controller clock cycle setting for SINAMICS G130, G150, S150 and S120 in
Chassis and Cabinet Modules formats.
Vector-type drive object with V/f control mode
For V/f control mode the table below shows the settable pulse frequencies f
attainable output frequencies f
equations (1) and (3) on the previous page (which must all be satisfied simultaneously).
Current controller
Settable pulse frequencies and associated max. output frequencies (exact, non-rounded values)
clock cycle
125 μs
(FW version ≥ 4.4
for SINAMICS S)
200 μs
(FW version ≥ 4.4
for SINAMICS S)
2
250 μs
SINAMICS G + S
3
400 μs
SINAMICS G + S
500 μs
1.00 kHz
SINAMICS G + S
83 Hz
1
Only with the license "High output frequency" that is available as option J01 for the SINAMICS S CompactFlash card
2
The factory settings for current controller clock cycle and pulse frequency are 250 μs and 2.00 kHz respectively for the
SINAMICS G and S converters below. Their maximum settable pulse frequency is 8.0 kHz:
- 380 V – 480 V 3AC: ≤ 250 kW / 490 A or 510 V – 720 V DC: ≤ 250 kW / 490 A
3
The factory settings for current controller clock cycle and pulse frequency are 400 μs and 1.25 kHz respectively for the
SINAMICS G and S converters below. Their maximum settable pulse frequency is 7.5 kHz:
- 380 V – 480 V 3AC: ≥ 315 kW / 605 A or 510 V – 720 V DC: ≥ 315 kW / 605 A
- 500 V – 600 V 3AC: All power ratings or
- 660 V – 690 V 3AC: All power ratings or
In the vector-type drive object with V/f control mode settable pulse frequencies and associated maximum attainable output
frequencies as a function of the current controller clock cycle setting for SINAMICS G130, G150, S150 and S120 in Chassis
and Cabinet Modules formats.
Notes:
·
The maximum attainable output frequency value for SINAMICS S converters described in this engineering
manual for vector-type drive objects in vector control mode is 550 Hz. With the license "High output
frequency", it is possible to increase the output frequency to maximum 650 Hz for SINAMICS S units. To
achieve this output frequency, a power unit is required, which is designed for a maximum pulse frequency of
8.0 kHz (table above), which is not operated in a parallel connection, and which operates with a current
controller clock cycle of 125 μs (settable on SINAMICS S with firmware version 4.4 or higher). In the case of
power units which are designed for a maximum pulse frequency of only 7.5 kHz (table above) and are not
operated in a parallel connection, the maximum attainable output frequency is 623 Hz. To obtain this output
frequency, a current controller clock cycle of 133.75 μs is required (settable on SINAMICS S with firmware
version 4.4 or higher) and a pulse frequency of 7.477 kHz.
·
By altering the current controller clock cycle in the range between 125 μs and 500 μs (with SINAMICS S) or
250 μs and 500 μs (with SINAMICS G), it is possible to set other pulse frequency values than those stated in
the table above, although it must be noted that the three equations (1) to (3) on the previous page must still
all be satisfied simultaneously. However, when units communicate in isochronous mode (e.g. via
isochronous PROFIBUS), the only permissible current controller clock cycle is 125 μs or whole multiples
Fundamental Principles and System Description
675 V – 900 V DC: All power ratings
890 V – 1035 V DC: All power ratings
as a function of the current controller clock cycle setting T
out max
2.50 kHz
208 Hz
2.00 kHz
166 Hz
1.25 kHz
2.50 kHz
104 Hz
208 Hz
2.00 kHz
166 Hz
675 V – 900 V DC: All power ratings
890 V – 1035 V DC: All power ratings
Engineering Information
Pulse
4.00 kHz
333 Hz
5.00 kHz
416 Hz
4.00 kHz
333 Hz
5.00 kHz
416 Hz
4.00 kHz
333 Hz
SINAMICS Engineering Manual – November 2015
and the associated maximum
in accordance with
I
8.0 kHz
550 Hz /
650 Hz
8.0 kHz
550 Hz /
650 Hz
7.5 kHz
550 Hz /
1
623 Hz
6.00 kHz
8.0 kHz
550 Hz /
500 Hz
650 Hz
23/528
Ó Siemens AG
1
1
1