Power requirement of supplementary components
The following components may be installed in the Cabinet Module and are connected down-circuit of the fuse
protection to the auxiliary voltage supply system. The power requirement must be added to the basic requirement of
the relevant Cabinet Module.
CU320-2 Control Unit
Voltage
Maximum power requirement (at 24 V DC) without taking
account of digital outputs and expansions in the option slot
Maximum fuse protection
Digital inputs:
·
Voltage
·
Low level (an open digital input is interpreted as "low") -3 V to +5 V
§
High level
§
Power consumption (typ. at 24 V DC)
Digital outputs (continued-short-circuit-proof):
§
Voltage
§
Maximum load current per digital output
Terminal Module 31 (TM31)
Voltage
Maximum power requirement (at 24 V DC) excluding digital
outputs and DRIVE-CLiQ supply
Digital outputs (continued-short-circuit-proof):
§
Voltage
§
Maximum load current per digital output
Sensor Module Cabinet-mounted 10 (SMC10)
Voltage
Maximum power requirement (at 24 V DC) excluding
encoder
Sensor Module Cabinet-mounted 20 (SMC20)
Voltage
Maximum power requirement (at 24 V DC) excluding
encoder
Sensor Module Cabinet-mounted 30 (SMC30)
Voltage
Maximum power requirement (at 24 V DC) excluding
encoder
AOP30 Advanced Operator Panel 30 (AOP30)
Voltage
Maximum power requirement (at 24 V DC):
- Without backlit display
- With maximum backlit display
SINAMICS S120 Cabinet Modules
24 V (20.4 V – 28.8 V) DC
1.0 A
20 A
12 floating digital inputs
8 bidirectional non-floating digital outputs / digital inputs
-3 V to +30 V
+15 V to +30 V
9 mA
8 bi-directional, non-floating digital outputs / digital inputs
24 V DC
500 mA
24 V DC (20.4 V – 28.8 V)
0.2 A
4 bi-directional, non-floating digital outputs / digital inputs
24 V DC
100 mA
24 V DC (20.4 V – 28.8 V)
0.2 A
24 V DC (20.4 V – 28.8 V)
0.2 A
24 V DC (20.4 V – 28.8 V)
0.2 A
24 V DC (20.4 V – 28.8 V)
100 mA
200 mA