For SINAMICS S150 cabinet units with line-side Active Line Module, the current controller clock cycle and the
pulse frequency of the Active Line Module are set at the factory to the values given in the table:
Line supply
voltage
380 V – 480 V 3AC
110 kW – 250 kW
315 kW
500 V – 690 V 3AC
75 kW – 315 kW
400 kW – 1200 kW
1)
With option L04 the ALM of the S150 cabinet unit 315 kW (380 V – 480 V) operates with a current controller clock cycle of 250 μs and a pulse frequency of 4.00 kHz
Factory setting of ALM current controller clock cycle and ALM pulse frequency for SINAMICS S150 cabinet units
Parameter p0092 (Clock synchronous operation pre-assignment/check) is the only means by which the factory
setting can be slightly changed. This parameter allows the current controller clock cycle to be changed from 400 μs to
375 μs to enable isochronous PROFIdrive operation. Changing this setting slightly increases the pulse frequency for
these devices from 2.50 kHz to 2.67 kHz.
Fundamental Principles and System Description
S150 output
Rectifier/regenerative
current
197 A – 447 A
1)
– 800 kW
549 A – 1262 A
86 A – 304 A
375 A – 1142 A
Engineering Information
Rated output current
210 A – 490 A
605 A – 1405 A
85 A – 330 A
410 A – 1270 A
SINAMICS Engineering Manual – November 2015
ALM current
ALM pulse
controller
frequency
clock cycle
250 μs
4.00 kHz
400 μs
2.50 kHz
250 μs
4.00 kHz
400 μs
2.50 kHz
109/528
Ó Siemens AG