Example for dimensioning a power cable
Boundary conditions:
Module: S120 Combi 4 axes Power Module with 20 kW infeed
Rated input current at 400 V
Ambient temperature: 45°C
Installation type: B2
Calculation/dimensioning:
With installation type B2 and a rated input current of 34 A
current-carrying capacity, a cable cross-section of 10 mm
With a derating factor of 0.91 for 45°C ambient temperature, the current-carrying capacity of
the selected power cable decreases to 36.4 A.
Result:
Under the given boundary conditions, a power cable with a cross-section of 10 mm
used.
13.7.4

Connectable conductor cross-sections for spring-loaded terminals

Table 13- 12 Spring-loaded terminals
Spring-loaded terminal type
1
Connectable conductor cross-
sections
Stripped length
Tool
13.7.5

Connectable conductor cross-sections for screw terminals

The type of screw terminal can be taken from the interface description of the particular
module.
Table 13- 13 Screw terminals
Screw terminal type
1
Connectable conductor cross-
sections
Stripped length
Tool
Tightening torque
SINAMICS S120 Combi
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
: 34 A (from the technical data)
AC
Flexible
8 to 9 mm
Screwdriver 0.4 x 2.0 mm
Rigid, flexible
With end sleeve, without plastic sleeve
With end sleeve, with plastic sleeve
7 mm
Screwdriver 0.4 x 2.0 mm
0.22 to 0.25 Nm
Cabinet design and EMC
13.7 Connection system
, from the table showing the
AC
is obtained.
2
0.08 mm
to 2.5 mm
2
0.08 mm
to 1.5 mm
2
0.25 mm
to 1.5 mm
2
0.25 mm
to 0.5 mm
2
can be
2
2
2
2
2
253

Advertisement

Table of Contents
loading

Table of Contents