Siemens G130 List Manual page 575

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p2271
Technology controller actual value inversion (sensor type) / Tech_ctrl act inv
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Integer16
P-Group: Technology
Not for motor type: -
Min
0
Description:
Setting to invert the actual value signal of the technology controller.
The inversion depends on the sensor type for the actual value signal.
Value:
0:
1:
Caution:
If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note:
The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal of the technology controller.
--> If the actual value increases as the motor speed increases, then p2271 should be set to 0 (no inversion).
--> If the actual value decreases as the motor speed increases, then p2271 should be set to 1 (the actual value signal
is inverted).
r2272
CO: Technology controller actual value scaled / Tech_ctrl act scal
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
- [%]
Description:
Display and connector output for the scaled actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, r2266, p2267, p2268, p2269, p2270, p2271
r2273
CO: Technology controller system deviation / Tec_ctrl sys_dev
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
- [%]
Description:
Displays the system deviation between the setpoint and actual value of the technology controller.
Dependency:
Refer to: p2263
p2274
Technology controller differentiation time constant / Tec_ctrl D comp T
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.000 [s]
Description:
Sets the time constant for the differentiation (D component) of the technology controller.
Note:
p2274 = 0: Differentiation is disabled.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
No inversion
Inversion actual value signal
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: 9_1
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: 9_1
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
60.000 [s]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7958
Unit selection: p0595
Expert list: 1
Factory setting
- [%]
Access level: 2
Func. diagram: 7958
Unit selection: p0595
Expert list: 1
Factory setting
- [%]
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]