r2132
CO: Actual alarm code / Actual alarm code
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the code of the last alarm that occurred.
Note:
0: No alarm present.
r2133[0...63]
Fault value for float values / Fault val float
All objects
Can be changed: -
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays additional information about the fault that occurred for float values.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2136, r3115
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2134[0...63]
Alarm value for float values / Alarm value float
All objects
Can be changed: -
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays additional information about the active alarm for float values.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125, r2145, r2146, r3121, r3123
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2135.0...15
CO/BO: Status word faults/alarms 2 / ZSW fault/alarm 2
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Display and BICO output for the second status word of faults and alarms.
Bit field:
Bit
00
01
02
12
13
14
15
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Fault encoder 1
Fault encoder 2
Fault encoder 3
Fault motor overtemperature
Fault power unit thermal overload
Alarm motor overtemperature
Alarm power unit thermal overload
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 2548
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
FP
-
-
-
8016
8021
8016
8021