B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 28 of 51)
ADDR
REGISTER NAME
860C
Breaker Failure 1 Timer 2 Pickup
860D
Breaker Failure 1 Use Timer 3
860E
Breaker Failure 1 Timer 3 Pickup
860F
Breaker Failure 1 Breaker Status 1 Phase A/3P
8610
Breaker Failure 1 Breaker Status 2 Phase A/3P
B
8611
Breaker Failure 1 Breaker Test On
8612
Breaker Failure 1 Phase Amp Hiset Pickup
8613
Breaker Failure 1 Neutral Amp Hiset Pickup
8614
Breaker Failure 1 Phase Amp Loset Pickup
8615
Breaker Failure 1 Neutral Amp Loset Pickup
8616
Breaker Failure 1 Loset Time
8617
Breaker Failure 1 Trip Dropout Delay
8618
Breaker Failure 1 Target
8619
Breaker Failure 1 Events
861A
Breaker Failure 1 Phase A Initiate
861B
Breaker Failure 1 Phase B Initiate
861C
Breaker Failure 1 Phase C Initiate
861D
Breaker Failure 1 Breaker Status 1 Phase B
861E
Breaker Failure 1 Breaker Status 1 Phase C
861F
Breaker Failure 1 Breaker Status 2 Phase B
8620
Breaker Failure 1 Breaker Status 2 Phase C
8621
...Repeated for Breaker Failure 2
8642
...Repeated for Breaker Failure 3
8663
...Repeated for Breaker Failure 4
8684
...Repeated for Breaker Failure 5
86A5
...Repeated for Breaker Failure 6
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
8A01
Digital Element 1 Name
8A09
Digital Element 1 Input
8A0A
Digital Element 1 Pickup Delay
8A0C
Digital Element 1 Reset Delay
8A0E
Digital Element 1 Block
8A0F
Digital Element 1 Target
8A10
Digital Element 1 Events
8A11
Digital Element 1 Pickup LED
8A12
Reserved (2 items)
8A14
...Repeated for Digital Element 2
8A28
...Repeated for Digital Element 3
8A3C
...Repeated for Digital Element 4
8A50
...Repeated for Digital Element 5
8A64
...Repeated for Digital Element 6
8A78
...Repeated for Digital Element 7
8A8C
...Repeated for Digital Element 8
8AA0
...Repeated for Digital Element 9
8AB4
...Repeated for Digital Element 10
8AC8
...Repeated for Digital Element 11
8ADC
...Repeated for Digital Element 12
8AF0
...Repeated for Digital Element 13
8B04
...Repeated for Digital Element 14
8B18
...Repeated for Digital Element 15
8B2C
...Repeated for Digital Element 16
B-36
RANGE
0 to 65.535
0 to 1
0 to 65.535
0 to 65535
0 to 65535
0 to 65535
0.001 to 30
0.001 to 30
0.001 to 30
0.001 to 30
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
---
0 to 1
---
0 to 65535
0 to 999999.999
0 to 999999.999
0 to 65535
0 to 2
0 to 1
0 to 1
---
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
s
0.001
F001
---
1
F126
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
---
F300
---
1
F102
---
---
F203
---
1
F300
s
0.001
F003
s
0.001
F003
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
---
F001
DEFAULT
0
1 (Yes)
0
0
0
0
1050
1050
1050
1050
0
0
0 (Self-reset)
0 (Disabled)
0
0
0
0
0
0
0
0
0 (Disabled)
"Dig Element 1"
0
0
0
0
0 (Self-reset)
0 (Disabled)
1 (Enabled)
0
GE Multilin