GE UR Series B30 Instruction Manual page 426

Bus differential system
Hide thumbs Also See for UR Series B30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 18 of 51)
ADDR
REGISTER NAME
4601
Phase Rotation
4602
Frequency and Phase Reference
4603
Frequency Tracking Function
Breaker Control (Read/Write Settings) (6 modules)
4700
Breaker 1 Function
B
4701
Breaker 1 Name
4704
Breaker 1 Mode
4705
Breaker 1 Open
4706
Breaker 1 Close
4707
Breaker 1 Phase A / Three-pole Closed
4708
Breaker 1 Phase B Closed
4709
Breaker 1 Phase C Closed
470A
Breaker 1 External Alarm
470B
Breaker 1 Alarm Delay
470D
Breaker 1 Pushbutton Control
470E
Breaker 1 Manual Close Recall Time
4710
Breaker 1 Out of Service
4711
Breaker 1 Block Open
4712
Breaker 1 Block Close
4713
Breaker 1 Phase A / Three-pole Opened
4714
Breaker 1 Phase B Opened
4715
Breaker 1 Phase C Opened
4716
Breaker 1 Operate Time
4717
Breaker 1 Events
4718
Reserved
4719
...Repeated for Breaker 2
4732
...Repeated for Breaker 3
474B
...Repeated for Breaker 4
4764
...Repeated for Breaker 5
477D
...Repeated for Breaker 6
FlexCurves A and B (Read/Write Settings)
4800
FlexCurve A (120 items)
48F0
FlexCurve B (120 items)
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
4C0A
User-Definable Display 1 Bottom Line Text
4C14
Modbus Addresses of Display 1 Items (5 items)
4C19
Reserved (7 items)
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
4D60
...Repeated for User-Definable Display 12
4D80
...Repeated for User-Definable Display 13
4DA0
...Repeated for User-Definable Display 14
4DC0
...Repeated for User-Definable Display 15
B-26
RANGE
0 to 1
0 to 5
0 to 1
0 to 1
---
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65.535
0 to 1
0 to 65.535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65.535
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
---
---
0 to 65535
---
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F106
---
1
F167
---
1
F102
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
---
1
F102
s
0.001
F003
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
---
1
F102
s
1
F001
ms
1
F011
ms
1
F011
---
1
F001
---
---
F202
---
---
F202
---
1
F001
---
---
F001
DEFAULT
0 (ABC)
0 (SRC 1)
1 (Enabled)
0 (Disabled)
"Bkr 1"
0 (3-Pole)
0
0
0
0
0
0
0
0 (Disabled)
0
0
0
0
0
0
0
70
0 (Disabled)
0
0
0
0
" "
" "
0
0
GE Multilin