GE UR Series B30 Instruction Manual page 141

Bus differential system
Hide thumbs Also See for UR Series B30:
Table of Contents

Advertisement

5 SETTINGS
Modbus over TCP/IP can also be used on any of the Ethernet ports. The listening TCP port 502 is reserved for Modbus
communications, and only in exceptional cases when
setting sets the TCP port used by Modbus on Ethernet. A
PORT NUMBER
over TCP/IP, meaning closes the Modbus TCP port. When it is set to 0, use the front panel or serial port to communicate
with the relay.
When a 0 value is involved in a change, the changes to the
B30 is restarted.
NOTE
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
e) DNP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 DNP PROTOCOL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
MODBUS TCP PORT NUMBER


COMMUNICATIONS
DNP PROTOCOL
 DNP CHANNELS
DNP ADDRESS:
65519
 DNP NETWORK
 CLIENT ADDRESSES
DNP TCP/UDP PORT
NUMBER: 20000
DNP UNSOL RESPONSE
FUNCTION: Disabled
DNP UNSOL RESPONSE
TIMEOUT: 5 s
DNP UNSOL RESPONSE
MAX RETRIES: 10
DNP UNSOL RESPONSE
DEST ADDRESS: 1
DNP CURRENT SCALE
FACTOR: 1
DNP VOLTAGE SCALE
FACTOR: 1
DNP POWER SCALE
FACTOR: 1
DNP ENERGY SCALE
FACTOR: 1
DNP PF SCALE
FACTOR: 1
DNP OTHER SCALE
FACTOR: 1
DNP CURRENT DEFAULT
DEADBAND: 30000
DNP VOLTAGE DEFAULT
DEADBAND: 30000
DNP POWER DEFAULT
DEADBAND: 30000
B30 Bus Differential System
is set to any other port. The
MODBUS TCP PORT NUMBER
setting take effect when the
MODBUS TCP PORT NUMBER
Range: see sub-menu below
Range: 0 to 65519 in steps of 1
Range: see sub-menu below
Range: 1 to 65535 in steps of 1
Range: Enabled, Disabled
Range: 0 to 60 s in steps of 1
Range: 1 to 255 in steps of 1
Range: 0 to 65519 in steps of 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
5.2 PRODUCT SETUP
MODBUS TCP
of 0 disables Modbus
5
5-17