Oscillography - GE UR Series B30 Instruction Manual

Bus differential system
Hide thumbs Also See for UR Series B30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
The last record is available as individual data items via communications protocols.
PRE-FAULT 1 TRIGGER: Specifies the FlexLogic™ operand to capture the pre-fault data. The rising edge of this
operand stores one cycle-old data for subsequent reporting. The element waits for the fault trigger to actually create a
record as long as the operand selected as
element resets and no record is created.
FAULT 1 TRIGGER: Specifies the FlexLogic™ operand to capture the fault data. The rising edge of this operand
stores the data as fault data and results in a new report. The trigger (not the pre-fault trigger) controls the date and time
of the report.
FAULT REPORT 1 #1 to FAULT REPORT 1 #32: These settings specify an actual value such as voltage or current
magnitude, true RMS, phase angle, frequency, temperature, etc., to be stored should the report be created. Up to 32
channels can be configured. Two reports are configurable to cope with variety of trip conditions and items of interest.
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 OSCILLOGRAPHY
5
Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic™ operand. Multiple oscillography records may be cap-
tured simultaneously.
The
NUMBER OF RECORDS
other factors such as sample rate and the number of operational modules. There is a fixed amount of data storage for oscil-
lography; the more data captured, the less the number of cycles captured per record. See the

RECORDS

OSCILLOGRAPHY

ple configurations with corresponding cycles/record.
5-42
PRE-FAULT 1 TRIGGER

OSCILLOGRAPHY
NUMBER OF RECORDS:
15
TRIGGER MODE:
MESSAGE
Automatic Overwrite
TRIGGER POSITION:
MESSAGE
50%
TRIGGER SOURCE:
MESSAGE
Off
AC INPUT WAVEFORMS:
MESSAGE
16 samples/cycle
 DIGITAL CHANNELS
MESSAGE
 ANALOG CHANNELS
MESSAGE
is selectable, but the number of cycles captured in a single record varies considerably based on
menu to view the number of cycles captured per record. The following table provides sam-
B30 Bus Differential System
is "On". If the operand remains "Off" for 1 second, the
5.2.8 OSCILLOGRAPHY
Range: 1 to 64 in steps of 1
Range: Automatic Overwrite, Protected
Range: 0 to 100% in steps of 1
Range: FlexLogic™ operand
Range: Off; 8, 16, 32, 64 samples/cycle
5 SETTINGS

ACTUAL VALUES
GE Multilin