Toshiba Q9 Installation And Operation Manual page 176

Asd
Table of Contents

Advertisement

F883
Ext. Comm. Cfg. 2
No Path — Direct Access Only
This parameter sets the Modbus RTU network characteristics: Baud Rate, Parity,
and Stop Bits. See the table below for the parameter settings.
Setting
Baud Rate
0
1
2400
2
3
4
4800
5
6
7
9600
8
9
10
19200
11
12
13
38400
14
15
2400
16
4800
17
9600
18
19200
19
38400
Note:
An improper parameter setting will result
in a Communication error.
Ext. Comm. Cfg. 3
No Path — Direct Access Only
This parameter Enables/Disables the network time-out timer. The timer is enabled
by setting this parameter to a non-zero value (1 – 255). The timer is disabled by
setting this value to zero.
Once started, the complete packet must be received before the timer expires or an
error will be incurred.
166
Parity
Stop Bits
Odd
Even
None
Odd
Even
None
Odd
Even
1
None
Odd
Even
None
Odd
Even
None
2
Direct Access Number — F883
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255 (only 0 – 19 effective)
Direct Access Number — F884
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Units — Seconds
Q9 ASD Installation and Operation Manual
F884