Toshiba Q9 Installation And Operation Manual page 103

Asd
Table of Contents

Advertisement

F222
RX2 (AI1) Reference 1
Program  Frequency Settings
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode or the Torque Control mode.
Note:
The Expansion IO Card Option 1 Option Board (P/N ETB003Z) is
required to use this terminal.
This parameter sets the RX2 (AI1) input level that is associated with
Frequency 1
when operating in the Speed Control mode.
RX2 (AI1) Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input at
the RX2 (AI1) input terminal:
• Program  Utility Group  Frequency Mode 1  RX2.
• Program  Utility Group  Command Mode  Terminal Block.
Speed Control
Perform the following setup to allow the system to perform Speed control from
the RX2 (AI1) input terminal:
• Set
RX2 (AI1) Frequency 1
• Set
RX2 (AI1) Reference 1
corresponds to the speed setting at
• Set
RX2 (AI1) Frequency 2
• Set
RX2 (AI1) Reference 2
corresponds to the speed setting at
• Provide a Run command (F and/or R).
Once set, as the RX2 (AI1) input voltage changes, the ASD output speed and/or
torque will vary in accordance with the above settings.
This parameter value is entered as -100% to +100% of the RX2 (AI1) input signal
range.
See the Expansion IO Card Option 1 Instruction Manual (P/N 58685) for more
information on the function of this terminal. See parameter
information on fine-tuning this terminal response.
RX2 (AI1) Frequency 1
Program  Frequency Settings
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode.
This parameter sets
RX2 (AI1) Frequency 1
with the setting of
RX2 (AI1) Reference 1
mode.
See RX2 (AI1) Reference 1 (F222) for more information on this setting.
Q9 ASD Installation and Operation Manual
(F223).
(F222) — the input analog signal level that
RX2 (AI1) Frequency
(F225).
(F224) — the input analog signal level that
RX Frequency
2.
F476
and is the frequency that is associated
when operating in the Speed Control
Direct Access Number — F222
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
RX2 (AI1)
1.
and
F477
for
Direct Access Number — F223
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F223
Frequency Settings
93

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents