F218
RX Reference 2
Program  Frequency Settings
This parameter is used to set the gain and bias of the RX input terminal when the
RX terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.
This parameter sets the RX input level that is associated with
when operating in the Speed control mode or is associated with the
Reference 2
when operating in the Torque Control mode.
This value is entered as -100% to +100% of the RX input signal range.
See RX Reference 1 (F216) for more information on this setting when used for
Speed control.
See RX Torque Reference 1 (F220) for more information on this setting when
used for Torque Control.
RX Frequency 2
Program  Frequency Settings
This parameter is used to set the gain and bias of the RX input terminal when the
RX terminal is used as the control input while operating in the Speed Control
mode.
This parameter sets
RX Frequency 2
the setting of
RX Reference 2
See RX Reference 1 (F216) for more information on this setting.
Q9 ASD Installation and Operation Manual
and is the frequency that is associated with
when operating in the Speed Control mode.
Direct Access Number — F218
Parameter Type — Numerical
Factory Default — +100
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
RX Frequency 2
RX Torque
Units — %
Direct Access Number — F219
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00.
Maximum — Max. Freq. (F011)
Units — Hz
F219
91