5.4 FLEXLOGIC™
Table 5–5: L90 FLEXLOGIC™ OPERANDS (Sheet 7 of 7)
OPERAND TYPE
OPERAND SYNTAX
UNAUTHORIZED
UNAUTHORIZED ACCESS
ACCESS ALARM
USER-
PUSHBUTTON x ON
PROGRAMMABLE
PUSHBUTTON x OFF
PUSHBUTTONS
Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID
(identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name/
ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in
the FlexLogic™ operands table above.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic™ are listed in the Flex-
Logic™ operators table.
Table 5–6: FLEXLOGIC™ GATE CHARACTERISTICS
GATES
NUMBER OF INPUTS
NOT
OR
AND
NOR
NAND
XOR
5
5-62
OPERAND DESCRIPTION
Asserted when a password entry fails while accessing a password-protected
level of the relay.
Pushbutton Number x is in the 'On' position
Pushbutton Number x is in the 'Off' position
OUTPUT IS '1' (= ON) IF...
1
input is '0'
2 to 16
any input is '1'
2 to 16
all inputs are '1'
2 to 16
all inputs are '0'
2 to 16
any input is '0'
2
only one input is '1'
L90 Line Differential Relay