5 SETTINGS
c) TRIP AND ALARM LEDS
!
PATH: SETTINGS
PRODUCT SETUP
# TRIP & ALARM LEDS
#
MESSAGE
The Trip and Alarm LEDs are on LED Panel 1. Each indicator can be programmed to become illuminated when the
selected FlexLogic™ operand is in the Logic 1 state.
d) USER-PROGRAMMABLE LED 1(48)
!
PATH: SETTINGS
PRODUCT SETUP
# USER-PROGRAMMABLE
# LED 1
MESSAGE
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic™ operand is in the Logic 1 state.
LEDs 1 through 24 inclusive are on LED Panel 2; LEDs 25 through 48 inclusive are on LED Panel 3.
Refer to the LED Indicators section in Chapter 4 for the locations of these indexed LEDs. This menu selects the operands
to control these LEDs. Support for applying user-customized labels to these LEDs is provided. If the
"Self-Reset" (default setting), the LED illumination will track the state of the selected LED operand. If the
is 'Latched', the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a communi-
cations channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5–2: RECOMMENDED SETTINGS FOR LED PANEL 2 LABELS
SETTING
PARAMETER
LED 1 Operand
SETTING GROUP ACT 1
LED 2 Operand
SETTING GROUP ACT 2
LED 3 Operand
SETTING GROUP ACT 3
LED 4 Operand
SETTING GROUP ACT 4
LED 5 Operand
SETTING GROUP ACT 5
LED 6 Operand
SETTING GROUP ACT 6
LED 7 Operand
Off
LED 8 Operand
Off
LED 9 Operand
BREAKER 1 OPEN
LED 10 Operand
BREAKER 1 CLOSED
LED 11 Operand
BREAKER 1 TROUBLE
LED 12 Operand
Off
Refer to the Control of Setting Groups example in the Control Elements section of this chapter for group activation.
GE Multilin
!"
USER-PROGRAMMABLE LEDS
TRIP LED INPUT:
Off
ALARM LED INPUT:
Off
!"
USER-PROGRAMMABLE LEDS
LED 1 OPERAND:
Off
LED 1 TYPE:
Self-Reset
SETTING
LED 13 Operand
LED 14 Operand
LED 15 Operand
LED 16 Operand
LED 17 Operand
LED 18 Operand
LED 19 Operand
LED 20 Operand
LED 21 Operand
LED 22 Operand
LED 23 Operand
LED 24 Operand
L90 Line Differential Relay
5.2 PRODUCT SETUP
!"
TRIP & ALARM LEDS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
!"
USER-PROGRAMMABLE LED 1(48)
Range: FlexLogic™ operand
Range: Self-Reset, Latched
PARAMETER
Off
BREAKER 2 OPEN
BREAKER 2 CLOSED
BREAKER 2 TROUBLE
SYNC 1 SYNC OP
SYNC 2 SYNC OP
Off
Off
AR ENABLED
AR DISABLED
AR RIP
AR LO
setting is
LED X TYPE
5
setting
LED X TYPE
5-27