GE C70 Instruction Manual page 551

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 23 of 65)
ADDR
REGISTER NAME
4143
DNP Object 21 Default Variation
4144
DNP Object 22 Default Variation
4145
DNP Object 23 Default Variation
4146
DNP Object 30 Default Variation
4147
DNP Object 32 Default Variation
4148
SCADA Protocol
Communications Actual Values (Read Only)
4160
Modbus Available TCP/IP Connections
4161
DNP Available TCP/IP Connections
4162
IEC Available TCP/IP Connections
4163
MMS Available TCP/IP Connections
4164
PMU Available TCP/IP Connections
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) Function
4169
Simple Network Time Protocol (SNTP) Server IP Address
416B
Simple Network Time Protocol (SNTP) UDP Port Number
Data Logger Commands (Read/Write Command)
4170
Data Logger Clear
Data Logger (Read/Write Setting)
4181
Data Logger Channel Settings (16 items)
4191
Data Logger Mode
4192
Data Logger Trigger
4194
Data Logger Rate
Clock (Read/Write Setting)
419F
Synchronizing Source
Clock (Read/Write Command)
41A0
Real Time Clock Set Time
Clock (Read/Write Setting)
41A2
SR Date Format
41A4
SR Time Format
41A6
IRIG-B Signal Type
41A7
Clock Events Enable / Disable
41A8
Time Zone Offset from UTC
41A9
Daylight Savings Time (DST) Function
41AA
Daylight Savings Time (DST) Start Month
41AB
Daylight Savings Time (DST) Start Day
41AC
Daylight Savings Time (DST) Start Day Instance
41AD
Daylight Savings Time (DST) Start Hour
41AE
Daylight Savings Time (DST) Stop Month
41AF
Daylight Savings Time (DST) Stop Day
41B0
Daylight Savings Time (DST) Stop Day Instance
41B1
Daylight Savings Time (DST) Stop Hour
Oscillography (Read/Write Setting)
41C0
Oscillography Number of Records
41C1
Oscillography Trigger Mode
41C2
Oscillography Trigger Position
41C3
Oscillography Trigger Source
41C5
Oscillography AC Input Waveforms
41D0
Oscillography Analog Channel n (16 items)
4200
Oscillography Digital Channel n (63 items)
Trip and Alarm LEDs (Read/Write Setting)
42B0
Trip LED Input FlexLogic Operand
42B2
Alarm LED Input FlexLogic Operand
GE Multilin
0 to 4294967295
0 to 4294967295
15 to 3600000
0 to 235959
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
0 to 3
---
1
0 to 3
---
1
0 to 3
---
1
1 to 5
---
1
0 to 5
---
1
0 to 2
---
1
0 to 4
---
1
0 to 2
---
1
0 to 2
---
1
0 to 5
---
1
0 to 4
---
1
0 to 1
---
1
---
1
1 to 65535
---
1
0 to 1
---
1
---
---
---
0 to 1
---
1
---
1
ms
1
0 to 3
---
1
---
1
---
1
---
1
0 to 2
---
1
0 to 1
---
1
–24 to 24
hours
0.5
0 to 1
---
1
0 to 11
---
1
0 to 6
---
1
0 to 4
---
1
0 to 23
---
1
0 to 11
---
1
0 to 6
---
1
0 to 4
---
1
0 to 23
---
1
3 to 64
---
1
0 to 1
---
1
0 to 100
%
1
---
1
0 to 4
---
1
0 to 65535
---
1
---
1
---
1
---
1
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F524
0 (1)
F523
0 (1)
F523
0 (1)
F001
1
F525
0 (1)
F629
0 (DNP 3.0)
F001
4
F001
2
F001
2
F001
5
F001
4
F102
0 (Disabled)
F003
0
F001
123
F126
0 (No)
F600
0
F260
0 (Continuous)
F300
0
F003
60000
F623
0 (None)
F050
0
F051
0
F052
0
F114
0 (None)
F102
0 (Disabled)
F002
0
F102
0 (Disabled)
F237
0 (January)
F238
0 (Sunday)
F239
0 (First)
F001
2
F237
0 (January)
F238
0 (Sunday)
F239
0 (First)
F001
2
F001
15
F118
0 (Auto.
Overwrite)
F001
50
F300
0
F183
2 (16 samples/
cycle)
F600
0
F300
0
F300
0
F300
0
B-31
B

Advertisement

Table of Contents
loading