Advertisement

5.2 PRODUCT SETUP
CYBERSENTRY SETTINGS THROUGH THE FRONT PANEL
PATH: SETTINGS
PRODUCT SETUP
 SECURITY
: This setting is applicable for Device Authentication only. This setting allows a user to login with a specific role, see
LOGIN
descriptions below. For the Supervisor role, the "Supervisor Role" setting should be enabled.
Whenever a new role is logged in, the user is prompted with a display to enter a password. Passwords must obey the
5
requirements specified at the beginning of the chapter in the Password Requirements section.The UR device supports five
roles. All roles have their corresponding passwords. The Observer role is the only role that does not require a password.
The roles are defined as follows:
Administrator: Complete read and write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
Engineer: Complete read and write access to all settings and commands with the exception of configuring Security set-
tings and Firmware upgrades. This role does not allow concurrent access.
Operator: The Operator has read/write access to all settings under the command menu/section. This role does not
exist offline.
Supervisor: This is only an approving role. This role's authentication commits setting changes submitted by Administra-
tor or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not approve changes
after the fact. Only Supervisor can set the Settings and Firmware Lock in the Security Settings. This role also has the
ability to forcefully logoff any other role and clear the security event log. This role can also be disabled, but only
through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role.
Observer: This role has read only access to all UR settings. This role allows unlimited concurrent access but it has no
download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel.
The Factory service role is not available and is intended for factory use only.
NOTE
Local Passwords
PATH: SETTINGS
PRODUCT SETUP
 CHANGE LOCAL
 PASSWORDS
5-18

SECURITY

LOGIN:
None
 CHANGE LOCAL
MESSAGE
 PASSWORDS
 SESSION
MESSAGE
 SETTINGS
 RESTORE DEFAULTS
MESSAGE
 SUPERVISORY
MESSAGE
SYSLOG IP ADDRESS:
MESSAGE
0.0.0.0
SYSLOG PORT NUMBER:
MESSAGE
514

SECURITY
CHANGE LOCAL PASSWORDS
LOGIN:
None
NEW PASSWORD:
MESSAGE
CONFIRM PASSWORD:
MESSAGE
C70 Capacitor Bank Protection and Control System
Range: Administrator, Engineer, Supervisor,
Operator, Factory (for factory use only), None
See below.
See page 5–19.
See page 5–19.
See page 5–20.
Range: 0.0.0.0, 255.255.255.255
Range: 1 to 65535
Range: 20 Alphanumeric Characters
Range: 20 Alphanumeric Characters
Range: 20 Alphanumeric Characters
5 SETTINGS