5.2 PRODUCT SETUP
The C70 supports the Distributed Network Protocol (DNP) version 3.0. DNP is enabled when the

SETUP
COMMUNICATIONS
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the C70 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the C70 at one time.
The DNP Channels sub-menu is shown below.
PATH: SETTINGS
PRODUCT SETUP
 DNP CHANNELS
The
DNP CHANNEL 1 PORT
for each channel. Once DNP is assigned to a serial port, DNP is the only protocol running on that port; Modbus or IEC
60870-5-103 are disabled. If DNP is assigned to RS485, the protocol must be set to DNP on the serial port configuration as
well, for the change to take effect. When the
DNP protocol can be used over TCP/IP on the Ethernet ports. When the
UDP," the channel 1 DNP protocol can be used over UDP/IP on the Ethernet ports. See the DNP appendix for information
on the DNP protocol.
5
Changes to these settings take effect when power has been cycled to the relay.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
NOTE
those protocols.
The
setting is the DNP slave address. This number identifies the C70 on a DNP communications link. Each
DNP ADDRESS
DNP slave should be assigned a unique address.
The C70 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which
the C70 can connect. The settings in this sub-menu are shown below.
PATH: SETTINGS
PRODUCT SETUP
 DNP NETWORK
 CLIENT ADDRESSES
The
DNP TCP/UDP PORT NUMBER
effect when the C70 is restarted.
5-38
DNP NUMBER OF PAIRED
MESSAGE
CONTROL POINTS: 0
DNP TCP CONNECTION
MESSAGE
TIMEOUT: 120 s
setting is set to DNP 3.0. The C70 can be used as a DNP slave device con-
PROTOCOL

COMMUNICATIONS
DNP CHANNEL 1 PORT:
NETWORK
DNP CHANNEL 2 PORT:
MESSAGE
COM2 - RS485
and
DNP CHANNEL 2 PORT
DNP CHANNEL 1(2) PORT

COMMUNICATIONS
CLIENT ADDRESS 1:
0.0.0.0
CLIENT ADDRESS 2:
MESSAGE
0.0.0.0
CLIENT ADDRESS 3:
MESSAGE
0.0.0.0
CLIENT ADDRESS 4:
MESSAGE
0.0.0.0
CLIENT ADDRESS 5:
MESSAGE
0.0.0.0
is for normal DNP operation. To close the port, set the port number to 0. The change takes
C70 Capacitor Bank Protection and Control System
Range: 0 to 32 in steps of 1
Range: 10 to 7200 s in steps of 1

DNP PROTOCOL
DNP CHANNELS
Range: NONE, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
Range: NONE, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP
settings select the communications port assigned to the DNP protocol
setting is set to "Network - TCP," the channel 1(2)
DNP CHANNEL 1 PORT

DNP PROTOCOL
DNP NETWORK CLIENT ADDRESSES
Range: standard IP address
Range: standard IP address
Range: standard IP address
Range: standard IP address
Range: standard IP address
5 SETTINGS
SETTINGS
PRODUCT
setting is set to "Network -
GE Multilin