CHAPTER 11: METERING
Voltage triggering
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Block
Range: any metering logic operand or shared operand
Default: Off
Assertion of the operand assigned to this setting blocks operation of the PMU frequency
triggering function.
Events
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the logging of PMU frequency triggering events in the
sequence of events recorder.
The figure shows the logic for the PMU frequency triggering function.
Figure 471: Frequency triggering logic
This Phasor Measurement Unit voltage triggering responds to abnormal voltage. Separate
thresholds are provided for low and high voltage. In terms of signaling its operation, the
element does not differentiate between the undervoltage and overvoltage events. The
trigger responds to the phase voltage signal of the PMU source. All voltage channels (A, B,
and C or AB, BC, and CA) are processed independently and can trigger the recorder. A
minimum voltage supervision of 0.1 pu is implemented to prevent pickup on a de-
energized circuit, similarly to the undervoltage protection element.
Select the Settings > Metering > Phasor Measurement Unit > Triggering > Voltage
Trigger menu to open the PMU voltage triggering window.
Figure 472: Voltage triggering configuration settings
The following settings are available for each PMU.
PHASOR MEASUREMENT UNIT
541