CHAPTER 7: PROTECTION
Contact input chatter detection
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
ID
Range: up to 12 alphanumeric characters
Default: Cont Ip 1
An alphanumeric ID can be assigned to a contact input for diagnostic, setting, and event
recording purposes. The "CONTACT IP 1" text in event records and FlexLogic operands
are replaced by the text programmed in this setting.
Debounce Time
Range: 1.5 to 16.0 ms in steps of 0.25
Default: 2.0 ms
This setting defines the time required for the contact to overcome contact bouncing
conditions. As this time differs for different contact types and manufacturers, program it
as a maximum contact debounce time (per manufacturer specifications) plus additional
margin to ensure proper operation.
Nominal Voltage
Range: 24 to 250 volts in steps of 1
Default: 125 volts
This setting specifies the range required to validate a closed contact input. This range is
fixed at 70 to 130% of this setting value, with an absolute minimum of 20 volts and an
absolute maximum of 285 volts.
Table 21: Nominal voltage setting for typical battery voltages
Nominal voltage
24 V
48 V
125 V
250 V
Events
Range: Enabled, Disabled
Default: Disabled
If this setting is "Enabled," every change in the contact input state triggers an event in
the event recorder.
Plus
The D90
has a chatter detection feature. When enabled, the IED monitors the number
of state changes that occur within a set duration. If this value exceeds a set value, then a
trouble condition is declared for the input and the
The input trouble alarm impacts relay functionality as follows:
FlexLogic operands: operand state is blocked
DNP 3.0 communications: reporting of the input is blocked
IEC 60870-5-104 communications: reporting of the input is blocked
IEC 61850 GSSE and IEC 61850 GOOSE: reporting of the input is blocked
Sequence of events recorder: reporting of the input is blocked
The trouble condition resets if the input undergoes no state changes for a duration equal
to twice the chatter time setting.
PROTECTION INPUTS AND OUTPUTS
Validation threshold
20 V
33.6 V
87.5 V
175 V
operand asserts.
CONTACT INPUT TROUBLE
391