The use of dynamic reach control by selection of a non-zero value for the
setting disables the subcycle operating time for that particular zone.
Delay
Range: 0.000 to 65.535 seconds in steps of 0.001
Default: 0.000 seconds
This setting allows the user to delay operation of the distance elements and implement
stepped distance protection. The distance element timers for zones 2 through 5 apply a
short dropout delay to cope with faults located close to the zone boundary when small
oscillations in the voltages or currents can inadvertently reset the timer. Zone 1 does not
need any drop-out delay since it is sealed-in by the presence of current.
Block
Range: any FlexLogic operand
Default: OFF
This setting enables the user to select a FlexLogic operand to block a given distance
element. VT fuse fail detection is one of the applications for this setting.
Events
Range: Enabled, Disabled
Default: Enabled
This setting enables and disables the logging of phase distance events in the sequence
of events recorder.
The following figure shows phase distance operation scheme logic for zone 1.
Figure 175: Phase distance zone 1 operation logic
The following figure shows the phase distance operation scheme logic for zone 2. The logic
is analogous for zones 3 through 5.
GROUPED PROTECTION ELEMENTS