Main Processor Module - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

WIRING
FASTPATH:

Main processor module

Ethernet port
CAUTION:
NOTE:
RS485 port
44
The table shows the dielectric strength of the UR
Table 1: Dielectric strength for UR
Function
Terminals
from
Power supply module
high (+), low (+), (–)
Power supply module
48 V DC (+) and (–)
Power supply module
relay terminals
Main CPU
RS485 port
Main CPU
RJ45 port
Main CPU
IRIG-B port
Front panel
USB port
Contact inputs/outputs
all
AC module
all
Communications module
RS45 ports
G.703 module
all except 1a, 8a
RS422 module
all except 1a, 8a
Filter networks and transient protection clamps are used in the hardware to prevent
damage caused by high peak voltage transients, radio frequency interference (RFI), and
electromagnetic interference (EMI).
The protective components can be damaged by application of any test voltage for a
period longer than the specified minute.
The main processor module in slot D contains ports for Ethernet communications, serial
RS485 communications, and IRIG-B connection.
The fiber optic communication ports allow for fast and efficient communications between
relays at 100 Mbps. Optical fiber can be connected to the relay supporting a wavelength of
1310 nm in multi-mode.
The optical fiber sizes supported are 50/125 µm and 62.5/125 µm. The fiber optic port is
designed such that the response times do not vary for any core that is 62.5 µm or less in
diameter. For optical power budgeting, splices are required every 1 km for the transmitter-
receiver pair. When splicing optical fibers, the diameter and numerical aperture of each
fiber must be the same. In order to engage or disengage the ST type connector, only a
quarter turn of the coupling is required.
Observing any fiber transmitter output can injure the eye.
Ensure the dust covers are installed when the fiber is not in use. Dirty or scratched
connectors can lead to high losses on a fiber link.
RS485 data transmission and reception are accomplished over a single twisted-pair wire
with transmit and receive data alternating over the same two wires. Through the use of
this port, continuous monitoring and control from a remote computer, SCADA system, or
Power Line Carrier (PLC) is possible.
Plus
-series module hardware.
Plus
-series hardware
to
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
Dielectric strength
2000 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
1500 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
1500 V AC for 1 minute
1000 V AC for 1 minute
1500 V AC for 1 minute