Resetting; Direct Inputs And Outputs - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

INPUTS/OUTPUTS
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic™ equations used to customize
the device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
There are 96 virtual outputs that can be assigned using FlexLogic. If not assigned, the output is forced to 'OFF' (Logic 0). An
ID also can be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings is
programmed as follows:
VIRTUAL OUTPUT 1 ID
VIRTUAL OUTPUT 1 EVENTS

5.9.5 Resetting

SETTINGS  INPUTS/OUTPUTS  RESETTING
 RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism holds all of the latched indicators or messages in the set state after the initiating condition
has cleared until a
The
command can be sent from the faceplate
RESET
5
programmed operand.
When the
command is received by the relay, two FlexLogic operands are created. These operands, which are stored
RESET
as events, reset the latches if the initiating condition has cleared. The three sources of
FlexLogic operand. Each individual source of a
RESET OP
,
(PUSHBUTTON)
RESET OP (COMMS)
selects the operand that creates the

5.9.6 Direct inputs and outputs

5.9.6.1 Direct inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS  DIRECT INPUT 1(32)
 DIRECT INPUT 1
These settings specify how the direct input information is processed.
DIRECT INPUT 1 NAME
DIRECT INPUT 1 DEVICE ID
identified here.
5-260
VIRTUAL OUTPUT 1
EVENTS: Disabled
: "Trip"
: "Disabled"
RESET OPERAND:
Off
command is received to return these latches (not including FlexLogic latches) to the reset state.
RESET
or
to identify the source of the command. The
RESET OP (OPERAND)
RESET OP (OPERAND)
DIRECT INPUT 1
NAME: Dir Ip 1
DIRECT INPUT 1
DEVICE ID: 1
DIRECT INPUT 1
BIT NUMBER: 1
DIRECT INPUT 1
DEFAULT STATE: Off
DIRECT INPUT 1
EVENTS: Disabled
— This setting allows the user to assign a descriptive name to the direct input.
— Represents the source of direct input 1. The specified direct input is driven by the device
Range: Disabled, Enabled
Range: FlexLogic operand
button, a remote device via a communications channel, or any
RESET
command also creates its individual operand
RESET
operand.
Range: up to 12 alphanumeric characters
Range: 1 to 16
Range: 1 to 32
Range: On, Off, Latest/On, Latest/Off
Range: Enabled, Disabled
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
commands each create the
RESET
RESET OP
setting here
RESET OPERAND