Settings Templates - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

CHAPTER 4: INTERFACES
4.
Site list / online window area
5.
Settings list / offline window area
6.
Software windows, with common tool bar
7.
Settings file data view windows, with common tool bar
8.
Workspace area with data view tabs
9.
Status bar
10. Quick action hot links
2
1
3
10
4
5

4.1.6 Settings templates

Settings file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An
example is a substation that has 10 similar feeders protected by 10 UR-series F60 relays.
In these situations, typically 90% or greater of the settings are identical among devices. The templates allow engineers to
configure and test these common settings, then lock them so that they are not available to users. For example, locked
down settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate on specific
settings.
The remaining settings (typically 10% or less) can be specified as editable and made available to field engineers installing
the devices. These are settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings are visible in the software. Settings templates can be
applied to both settings files (settings file templates) and online devices (online settings templates). The functionality is
identical for both purposes.
Settings file conversion from previous firmware versions is supported.
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 4-1: EnerVista UR Setup software window
6
9
8
ENERVISTA SOFTWARE INTERFACE
7
4
842786A2.CDR
4-3

Advertisement

Table of Contents
loading