GE D30 Instruction Manual page 32

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

SPECIFICATIONS
Polarizing voltage:
Operating current:
Level sensing:
Zero-sequence:
Negative-sequence:
Restraint, K:
Characteristic angle:
Limit angle:
2
Angle accuracy:
Offset impedance:
Pickup level:
Dropout level:
Operation time:
PHASE UNDERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Curve shapes:
Curve multiplier:
Curve timing accuracy at <0.90 x pickup:
AUXILIARY UNDERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Curve shapes:
Curve multiplier:
Curve timing accuracy at <0.90 x pickup:
PHASE OVERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Operate time:
Timer accuracy:
NEUTRAL OVERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Reset delay:
Curve timing accuracy at >1.1 pickup: ±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate
Operate time:
AUXILIARY OVERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Pickup delay:
Reset delay:
Timer accuracy:
Operate time:
2-22
V_2
I_2
|I_0| – K × |I_1|
|I_2| – K × |I_1|
0.000 to 0.500 in steps of 0.001
0 to 90° in steps of 1
40 to 90° in steps of 1, independent for forward and reverse
±2°
0.00 to 250.00 Ω in steps of 0.01
0.015 to 30.000 pu in steps of 0.01
97 to 98%
<16 ms at 3 × pickup at 60 Hz
0.000 to 3.000 pu in steps of 0.001
102 to 103% of pickup
±0.5% of reading from 10 to 208 V
GE IAV Inverse;
Definite Time (0.1s base curve)
Time dial = 0.00 to 600.00 in steps of 0.01
±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate
0.000 to 3.000 pu in steps of 0.001
102 to 103% of pickup
±0.5% of reading from 10 to 208 V
GE IAV Inverse, Definite Time
Time Dial = 0 to 600.00 in steps of 0.01
±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0.00 to 600.00 in steps of 0.01 s
<30 ms at 1.10 × pickup at 60 Hz
±3% of operate time or ±1/4 cycle (whichever is greater)
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0.00 to 600.00 s in steps of 0.01 (definite time) or user-defined curve
0.00 to 600.00 s in steps of 0.01
<30 ms at 1.10 pickup at 60 Hz
0.000 to 3.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading from 10 to 208 V
0 to 600.00 s in steps of 0.01
0 to 600.00 s in steps of 0.01
±3% of operate time or ±1/4 cycle (whichever is greater)
<30 ms at 1.10 × pickup at 60 Hz
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL