GE D30 Instruction Manual page 306

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

GROUPED ELEMENTS
5
The power swing detect element provides both power swing blocking and out-of-step tripping functions. The element
measures the positive-sequence apparent impedance and traces its locus with respect to either two or three user-
selectable operating characteristic boundaries. Upon detecting appropriate timing relations, the blocking and/or tripping
indications are given through FlexLogic operands. The element incorporates an adaptive disturbance detector. This
5-174
POWER SWING QUAD REV
REACH MID: 60.00 Ω
POWER SWING QUAD REV
REACH OUT: 70.00 Ω
POWER SWING REV
RCA: 75°
POWER SWING OUTER
LIMIT ANGLE: 120°
POWER SWING MIDDLE
LIMIT ANGLE: 90°
POWER SWING INNER
LIMIT ANGLE: 60°
POWER SWING OUTER
RGT BLD: 100.00 Ω
POWER SWING OUTER
LFT BLD: 100.00 Ω
POWER SWING MIDDLE
RGT BLD: 100.00 Ω
POWER SWING MIDDLE
LFT BLD: 100.00 Ω
POWER SWING INNER
RGT BLD: 100.00 Ω
POWER SWING INNER
LFT BLD: 100.00 Ω
POWER SWING PICKUP
DELAY 1: 0.030 s
POWER SWING RESET
DELAY 1: 0.050 s
POWER SWING PICKUP
DELAY 2: 0.017 s
POWER SWING PICKUP
DELAY 3: 0.009 s
POWER SWING PICKUP
DELAY 4: 0.017 s
POWER SWING SEAL-IN
DELAY: 0.400 s
POWER SWING TRIP
MODE: Delayed
POWER SWING BLK:
Off
POWER SWING
TARGET: Self-Reset
POWER SWING
EVENTS: Disabled
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 40 to 90° in steps of 1
Range: 40 to 140° in steps of 1
Range: 40 to 140° in steps of 1
Range: 40 to 140° in steps of 1
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Early, Delayed
Range: Flexlogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL