Fu1-07: Stop Mode - LG SV-iS5 Instruction Manual

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

Chapter 6 - Parameter Description [FU1]
Output Frequency
Acc. Pattern
[Accel/Decel Pattern: ' Linear' ]
Output Frequency
Acc. Pattern
[Accel/Decel Pattern: ' S-curve' ]
Output Frequency
Acc. Pattern
[Accel/Decel Pattern: ' U-curve' ]

FU1-07: Stop Mode

FU1?
Stop mode
07
Decel
Factory Default:
Decel
Sets the stopping method for the inverter.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Time
Dec. Pattern
Time
Dec. Pattern
Time
Dec. Pattern
07
0
0
88
Setting Range
LCD
7-Seg
0
Decel
Inverter stops by the deceleration pattern.
Inverter stops with DC injection braking.
Inverter outputs DC voltage when the
Dc-brake
1
frequency reached the DC injection
braking frequency set in FU1-08 during
decelerating.
Free-run
Inverter cuts off its output immediately
2
(Coast to stop)
when the stop signal is commanded.
Output Frequency
Output Voltage
Stop Command
ON
FX-CM
[Stop Mode: ' Decel' ]
Output Frequency
FU1-08
Output Voltage
FU1-10
[DCBr Value]
Stop Command
ON
FX-CM
[Stop Mode: ' D c-brake' ]
Description
Time
Time
Time
Time
t1: FU1-09
t2: FU1-11
Time
t1
t2
Time

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents