I/O-45: Fault Output Relay (30A, 30B, 30C)
I/O? Relay mode
45
010
Factory Default:
010
This function is used to allow the fault output relay to
operate when a fault occurs. The output relay terminal is
30A, 30B, 30C where 30A-30C is a norm ally open
contact and 30B-30C is a normally closed contact.
Settin
Bit
Display
g
0
000
Bit 0
(LV)
1
001
0
000
Bit 1
(Trip)
1
010
0
000
Bit 2
(Retry)
1
100
When several faults occurred at the same time, Bit 0 has
the first priority.
Related Functions:
DRV-12 [Fault Display]
FU2-26 [Retry number]
I/O-46: Inverter Number
I/O-47: Baud Rate
I/O?
Inv No.
46
1
Factory Default:
1
This code sets the inverter number. This number is used
in communication between inverter and communication
board.
I/O?
Baud rate
47
9600 bps
Factory Default:
9600
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
45
010
010
Description
Fault output relay does not
operate at ' Low voltage' trip.
Fault output relay operates at
' Low voltage' trip.
Fault output relay does not
operate at any fault.
Fault output relay operates at
any fault except ' Low voltage'
and ' BX' (inverter disable) fault.
Fault output relay does not
operate regardless of the retry
number.
Fault output relay operates
when the retry number set in
FU2-26 decreases to 0 by
faults.
46
1
1
47
9600
9600
Chapter 6 - Parameter Description [I/O]
This code sets the communication speed. This is used in
communication between inverter and communication
board.
I/O-48: Operating at Loss of Freq. Reference
I/O-49: Waiting Time after Loss of Freq.
Reference
I/O?Lost command
48
None
Factory Default:
None
There are two kinds of loss of frequency reference. One
is the loss of digital frequency reference and the other is
of analog frequency reference.
Loss of digital frequency reference is applied when DRV-
04 [Frequency Mode] is set to ' Keypad-1' or ' Kepad-2' .
At this time, the ' Loss' means the communication error
between inverter and keypad or communication board
during the time set in I/O-49.
Loss of analog frequency reference is applied when
DRV-04 [Frequency Mode] is set to other than ' Keypad-
1' or ' Kepad-2' . At this time, the ' Loss' is determined by
the criteria set in I/O-11 [Criteria for Analog Input Signal
Loss].
Setting Range
LCD
7-Seg
None
0
FreeRun
1
(Coast to stop)
Stop
2
I/O?
Time out
49
1.0 sec
Factory Default:
1.0 sec
This is the time inverter determines whether there is a
frequency reference or not. If there is no frequency
reference satisfying I/O-11 during this time, inverter
determines that it has lost of frequency reference.
Related Functions:
DRV-04 [Frequency Mode]
I/O-11 [Criteria for Analog Signal Loss]
133
48
0
0
Description
Inverter keeps on operating at the
previous frequency.
Inverter cuts off its output.
Inverter stops with Decel time (DRV-
02) and Decel pattern (FU1-26).
49
1.0
1.0