F964

Analog Function Assigned Object 21

Program My Function My Function Analog
This parameter plays a role in the setup of the My Function feature by
selecting the functionality to which the adjustment of
Settings:
0 — Disabled (None)
1 — Acceleration Rate
2 — Upper-Limit Frequency
3 — Acceleration Multiplication Factor
4 — Deceleration Multiplication Factor
5 — Manual Torque Boost
6 — Over-Current Stall (F601)
7 — Thermal Protection
8 — Speed Loop Proportional Gain (F460)
9 — Drooping Gain (F320)
10 — PID Proportional Gain (F362)
See the My Function Instruction Manual (P/N E6581335) for a complete
description of the setup requirements and operational information of the Analog
Function Assigned Object parameter.

Monitor Output Function 11

Program My Function My Function Monitor
This parameter plays a role in the setup of the My Function feature by
establishing the function that is to be recorded and output as the Peak,
Minimum, or Average value as selected at parameter F966.
Select the Monitor Display Input Setting number from
output the corresponding function.
Use the Communication Number if operating using communications.
See the My Function Instruction Manual (P/N E6581335) for a complete
description of the setup requirements and operational information of the
Monitor Output Function parameter.

Monitor Output Function Command 11

Program My Function My Function Monitor
This parameter plays a role in the setup of the My Function feature by allowing
the user to select the Peak, Minimum, or Normal (Avg.) value of the
parameter
F965
selection to be recorded and output as a monitored function.
Settings:
0 — Normal
1 — Peak
2 — Minimum
See the My Function Instruction Manual (P/N E6581335) for a complete
description of the setup requirements and operational information of the
Monitor Output Function parameter.
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Direct Access Number — F964
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
F962
is applied.
Direct Access Number — F965
Parameter Type — Selection List
Factory Default — 2000
Changeable During Run — Yes
Table 10 on pg. 241
to
Direct Access Number — F966
Parameter Type — Selection List
Factory Default — Normal
Changeable During Run — Yes
F966
227