V/F 5-Point Setting Voltage 2 / V/F 5-Point Setting Frequency 3; V/F 5-Point Setting Voltage 3; V/F 5-Point Setting Frequency 4; V/F 5-Point Setting Voltage 4 - Toshiba H9 ASD Installation And Operation Manual

Adjustable low voltage heavy duty industrial speed drive
Hide thumbs Also See for H9 ASD:
Table of Contents

Advertisement

F193
V/f 5-Point Setting Voltage 2
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 2 establishes the output voltage level that is to
be associated with the frequency setting of
Frequency 2).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this setting.
V/f 5-Point Setting Frequency 3
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 3 sets the frequency to be associated with
the voltage setting of parameter
See
F190
and
F191
for additional information on this setting.

V/f 5-Point Setting Voltage 3

Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 3 establishes the output voltage level that is to
be associated with the frequency setting of
Frequency 3).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this setting.

V/f 5-Point Setting Frequency 4

Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 4 sets the frequency to be associated with
the voltage setting of parameter
See
F190
and
F191
for additional information on this setting.

V/f 5-Point Setting Voltage 4

Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 4 establishes the output voltage level that is to
be associated with the frequency setting of
Frequency 4).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this setting.
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
F192
(V/f 5-Point Setting
F195
(V/f 5-Point Setting Voltage 3).
F194
(V/f 5-Point Setting
F197
(V/f 5-Point Setting Voltage 4).
F196
(V/f 5-Point Setting
Direct Access Number — F193
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
Direct Access Number — F194
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F195
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
Direct Access Number — F196
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F197
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
F197
103