F294
Preset Speed 15
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1111 and is
identified as Preset Speed 15. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).

PWM Carrier Frequency

Program Special Carrier Frequency
This parameter sets the frequency of the pulse width modulation signal applied
to the motor.
When operating in the Vector Control mode the carrier
Note:
frequency should be set to 2.2 kHz or above
Note:
If the PWM carrier frequency is set at 2.0 kHz or above, it cannot
be decreased below 2.0 kHz while running. If the PWM carrier
frequency is set at 1.9 kHz or below, it cannot be increased above
2.0 kHz while running. Either change requires that the ASD be
stopped and restarted for the changes to take effect.

Auto Restart Selection

Program Protection Retry/Restart
This parameter Enables/Disables the ability of the drive to start into a spinning
motor when the ST – CC connection opens momentarily and is then closed
(Break/Make ST) or after a power interruption (momentary power failure).
Settings:
0 — Off
1 — Enabled (at Power Failure)
2 — Enabled (at Make-Break ST-CC)
3 — Enabled (at Make-Break ST-CC or Power Failure)
4 — Enabled (at Run)
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
F018
for more information on
.
Direct Access Number — F294
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Direct Access Number — F300
Parameter Type — Numerical
Factory Default — 2.200
Changeable During Run — No
Minimum — 1.0
Maximum — (ASD-Dependent)
Units — kHz
Direct Access Number — F301
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
F301
133