Toshiba GRE110 Instruction Manual page 261

Overcurrent protection relay
Table of Contents

Advertisement

08 Diagnostic
Response Data
SC
Response Data Field
00
Echo Request Data (2Bytes)
01
<not supported>
02
Diagnostic Register Contents (2Bytes)
bit0
IN SERVICE (LED)
bit1
TRIP (LED)
bit2
ALARM (LED)
bit3
RELAY FAIL (LED)
bit4
<Reserved>
bit5
<Reserved>
bit6
<Reserved>
bit7
<Reserved>
bit8
3-phase current balance alarm
bit9
CB contact status alarm
bit10 CB operation number alarm
bit11 CB operating time alarm
bit12 ∑I
y
bit13 trip circuit supervision alarm
bit14 <Reserved>
bit15 <Reserved>
03-
<not supported>
17 Report Slave ID
Response Data
Byte Count (1byte)
Slave ID (17bytes)
GRE110-401A-00-10
Run Indicator Status (1byte)
43 Read Device Identification (SC:14)
Response Data
Param OID
01
00
TOSHIBA
01
GRE110-401
02
A
02
03
<Non>
04
GRE110
05
401A-10-10
06
Motor Protection
07-
<Reserved>
03
80
<SPASE>
81
GS1EM1-02-A
04
<not supported>
monitoring alarm
 262 
Description
Return Query Data
Return Diagnostic Register
18bytes
Relay type and model ID
ASCII
0x00=out of service, 0xFF=in service
Basic device identification
Vendor Name
Product Code
Major Minor Revision
Regular device identification
Vendor URL
Product Name
Model Name
User Application Name
Reserved
Extended device identification
Software version
One specific identification object
6 F 2 T 0 1 7 2

Hide quick links:

Advertisement

Table of Contents
loading