Operating current check

Figure 6.5.1 shows a testing circuit. The operating current value is checked by increasing or
decreasing the magnitude of the current applied.
+
Single-phase
current
source
+
power
supply
Figure 6.5.1 Operating Current Value Test Circuit
The output signal of testing element is assigned a configurable LED.
The output signal numbers of the elements are as follows:
Element
OC1-A
OC2-A
OC3-A
OC4-A
• Enter the signal number to observe the operation at the LED as shown in Section 6.5.1 and
press the ENTER key.
• Apply a test current and change the magnitude of the current applied and measure the value
at which the element operates.
Check that the measured value is within 5% of the setting value.