306
Info.
The controller-module serial number in Storage Controller flash memory was found to be invalid when
compared to the serial number in the controller-module FRU ID SEEPROM. The valid serial number has
been recovered automatically.
Recommended actions
No action is required.
307
Critical
A temperature sensor on a controller FRU detected an over-temperature condition that caused the controller
to shut down.
Recommended actions
Check that the storage system's fans are running.
Check that the ambient temperature is not too warm. The enclosure operating range is 5 C–40 C
(41 F–104 F).
Check for any obstructions to the airflow.
Check that there is a module or blank plate in every module slot in the enclosure.
If none of the above explanations apply, replace the controller module that logged the error.
308
Info.
The default host port speed has changed from 4 Gbit/sec to 2 Gbit/sec because the controller module's
HIM has a Broadcom PBC.
Recommended actions
No action is required.
309
Info.
Normally when the Management Controller is started, the IP data are obtained from the midplane FRU ID
SEEPROM where it is persisted. If the system is unable to write it to the SEEPROM the last time it changed,
a flag is set in flash memory. This flag is checked during startup, and if set, this event is logged and the IP
data that is in flash memory is used. The only time that this would not be the correct IP data would be if the
controller module was swapped and then whatever data are in the controller's flash memory is used.
Recommended actions
No action is required.
310
Info.
After a rescan, back-end discovery and initialization of data for at least one EMP (Enclosure Management
Processor) has completed. This event is not logged again when processing completes for other EMPs in the
system.
Recommended actions
No action is required.
31 1
Info.
This event is logged when a user initiates a ping of a host via the iSCSI interface.
Recommended actions
If the ping operation failed, check connectivity between the storage system and the remote host.
44
Event descriptions