[ II Restrictions ]

[7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected

(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
(2) Cautions
1) Be sure to connect a system controller.
2) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote
controller addresses that are smaller than those of the in-
door units that are connected to the ME remote control-
ler.
4) No more than 2 ME remote controllers can be connected
to a group of indoor units.
5) No more than 2 MA remote controllers can be connected
to a group of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
7) Replace the power jumper connector of the control board
from CN41 to CN40 on only one of the outdoor units.
(not required if power to the transmission line for central-
ized control is supplied from a controller with a power-
supply function, such as GB-50ADA)
8) Provide an electrical path to ground for the S terminal on
the terminal block for centralized control on only one of
the outdoor units.
9) A transmission booster must be connected to a system
in which the total number of connected indoor units ex-
ceeds 20.
HWE10040
L11
Leave the male
Leave the male
Move the male connector
connector on
connector on
from CN41 to CN40.
CN41 as it is.
CN41 as it is.
SW2-1 OFF ON
SW2-1 OFF ON
SW2-1 OFF ON
OS2
OS1
OC
53
52
51
TB3
TB3
TB3
M1 M2
M1 M2
M1 M2
TB7
TB7
TB7
M1 M2
S
M1 M2
S
M1 M2
To be left
To be left
unconnected
unconnected
L21
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW2-1 OFF ON
SW2-1 OFF ON
OS2
OS1
OC
56
55
54
TB3
TB3
TB3
M1 M2
M1 M2
M1 M2
TB7
TB7
TB7
M1 M2
S
M1 M2
S
M1 M2
To be left
To be left
unconnected
unconnected
L12
Group
IC
01
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
To be connected
MA
L22
Group
Group
IC
03
TB5
TB5
TB15
M1 M2
S
1 2
M1 M2
S
A B
A B
To be left
unconnected
104
MA
RC
Note1 When only the LM adapter is connected,
leave SW2-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 208/230V.
Note1
System controller
A B S
10) A transmission booster is required in a system to which
more than 16 indoor including one or more indoor units
of the 200 model or above are connected.
11) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Same as [5] 4.
3) MA remote controller wiring
Same as [5] 1.
4) ME remote controller wiring
Same as [5] 1.
5) Maximum line distance via outdoor unit
2
(1.25mm
Same as [5] 4.