[ II Restrictions ]

[7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected

(1) Sample control wiring
(2) Cautions
1) Be sure to connect a system controller.
2) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote
controller addresses that are smaller than those of the in-
door units that are connected to the ME remote control-
ler.
4) No more than 2 ME remote controllers can be connected
to a group of indoor units.
5) No more than 2 MA remote controllers can be connected
to a group of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
7) Replace the power jumper connector of the control board
from CN41 to CN40 on only one of the outdoor units.
8) Provide an electrical path to ground for the S terminal on
the terminal block for centralized control on only one of
the outdoor units.
9) A transmission booster is required in a system to which
more than 16 indoor including one or more indoor units
of the 200 model or above are connected.
10) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
HWE08110
L11
CN41
CN40 Replace
Leave the male
SW2-1 OFF ON
connector on CN41 as it is.
SW2-1 OFF ON
OS
OC
52
51
TB3
TB3
M1M2
M1M2
TB7
TB7
M1M2
S
M1M2
S
Not
connect
Connect
L21
Leave the male
Leave the male
connector on CN41 as it is.
connector on CN41 as it is.
SW2-1 OFF ON
SW2-1 OFF ON
OS
OC
55
54
TB3
TB3
M1M2
M1M2
TB7
TB7
S
S
M1M2
M1M2
Not
connect
Not
connect
Note1
System controller
A B S
L12
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1 M2
S
1 2
M1 M2
S
1 2
A B
MA
L22
Group
Group
IC
IC
03
04
TB5
TB5
TB15
TB15
M1 M2
S
1 2
M1 M2
S
1 2
A B
A B
104
MA
RC
Note1 When only the LM adapter is connected,
leave SW2-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 220/240V.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Same as [5] 4.
3) MA remote controller wiring
Same as [5] 1.
4) ME remote controller wiring
Same as [6].
5) Maximum line distance via outdoor unit
2
(1.25mm
Same as [5] 4.
- 38 -
Group
IC
06
TB5
TB15
M1 M2
S
1 2
A B
106
RC
IC
05
TB5
TB15
1 2
M1 M2
S
[AWG16] or more)
GB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hp250yhm-aHp500yshm-aPuhy-hp400

Table of Contents