An Example Of A System To Which Both Ma Remote Controller And Me Remote Controller Are Connected - Mitsubishi Electric PURY-WP200 Service Manual

Table of Contents

Advertisement

[ II Restrictions ]

[7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected

(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS
Note3
52
TB3
M1M2
TB7
M1M2
S
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS
Note3
55
TB3
M1 M2
TB7
S
M1 M2
(2) Cautions
1)
Be sure to connect a system controller.
2)
ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
3)
Assign to the indoor units connected to the MA remote controller ad-
dresses that are smaller than those of the indoor units that are con-
nected to the ME remote controller.
4)
No more than 2 ME remote controllers can be connected to a group
of indoor units.
5)
No more than 2 MA remote controllers can be connected to a group
of indoor units.
6)
Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
7)
Replace the power jumper connector of the control board from CN41
to CN40 on only one of the outdoor units.
(not required if power to the transmission line for centralized control
is supplied from a controller with a power-supply function, such as
GB-50ADA)
8)
Provide an electrical path to ground for the S terminal on the terminal
block for centralized control on only one of the outdoor units.
9)
When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
HWE1113B
L11
Move the male connector
from CN41 to CN40.
SW2-1 OFF ON
OC
HB
51
53
TB3
TB02
M1M2
M1M2
S
TB7
M1M2
S
To be left
To be connected
unconnected
L21
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OC
HB
54
56
TB3
TB02
M1 M2
M1 M2
S
TB7
To be left
S
M1 M2
unconnected
To be left
unconnected
Note1
System controller
A B S
L12
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1M2
S
1 2
M1M2
S
1 2
A1 B2
MA
L22
Group
Group
IC
IC
03
04
TB5
TB5
TB15
TB15
M1M2
S
1 2
M1M2
S
1 2
A1 B2
A1 B2
104
MA
RC
Note1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
Note2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
Note3 The figures above show a system to which two outdoor units are connected,
but only a single outdoor unit can be connected in an HVRF system.
When the P200 and P250 mod-
els are not included in the con-
nected indoor units
When the P200and P250 models
are included in the connected in-
door units
10) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
- 42 -
Group
IC
06
TB5
TB15
M1M2
S
1 2
A1 B2
106
RC
IC
05
TB5
TB15
M1M2
S
1 2
Number of transmission booster
(sold separately) required
1 unit
2 units
15 - 34
35 - 50
units
units
11 - 26
27 - 42
units
units
3 units
-
43 - 50
units
GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wp250yjm-aCmb-wp108v-g

Table of Contents