Indoor Parameters - Haier MRV II Instruction Manual

Table of Contents

Advertisement

1.3.5 Dip switch on inverter board
inspection of operation
SW1-1
without load
SW1-2
pre-set
SW1-3
pre-set
communication failure
SW1-4
alarm with connecting
board serial port
SW1-5
pre-set
SW1-6
pre-set
pre-set
SW2-1
SW2-2
pre-set
SW2-3
pre-set
pre-set
SW2-4

1.4 Indoor parameters

SW9
0
1
2
3
function
SW11
3
indoor communication checking
4
indoor abnormal
5
indoor capacity
6
indoor EEV open angle
7
air inlet temp.
8
indoor gas pipe temp.
9
indoor liquid pipe temp.
pre-set
10-15
cannot run without load, set when out of factory
0
can run without load
1
set as OFF when out of factory
0
set as OFF when out of factory
1
0
alarm, set when out of factory
not alarm, set when out of factory
1
set as OFF when out of factory
0
0
set as OFF when out of factory
set as OFF when out of factory
0
set as OFF when out of factory
0
set as OFF when out of factory
0
set as OFF when out of factory
0
SW10
0-15
LED3, LED4, indoor available, display 1111; indoor unavailable, display ----
display indoor failure code; no failure, display 0
LED3, LED4, display indoor capacity, 1.5HP displays 1.5
LED2, LED3, LED4 display valve open angle
LED2, LED3, LED4 display air inelt temp. -2 degree displays -02
LED2, LED3, LED4 display air inelt temp. -2 degree displays -02
LED2, LED3, LED4 display air inelt temp. -2 degree displays -02
- 98 -
address
1-16
17-32
33-48
49-64
control description
Part 3