Haier MRV II Instruction Manual page 51

Table of Contents

Advertisement

exhibition
outdoor
does not
heat, or
2
heating
effect is not
good
one
wired
controller
control
one
indoor, wired
controller
3
shows 8888
circularly
and can not
recover
No.
trouble
pipe is too long ,
or
the
height
between
indoor
units is more than
standard
Outdoor
4-way
valve
turbulence results
in
high/low
pressure too low.
action of outdoor
EEV action is not
good, or outdoor
EEV
being
damaged due to
the
wrong
connection of air
suction
temp.
sensor
SW01
on
PCB
does not at "0"
CN30
on
PCB
does not
be
short connected
trouble
- 52 -
shooting
change the
units
according
of the use
manual, or
add
a
electric
heater
in
change
4-way
valve
connect
air suction
temp.
sensor
reliably or
change
EEV
of
outdoor
change
SW01
to
" 0 "
make
CN30
short
connection
trouble
diagnose method)
high/low pressure
are too low, and
can not rise even
supply refrigerant,
indoor TC1/TC2 is
too low, condenser
pipes are warm
EEV can not adjust
normally,
and
usually show open
or close fully, you
can
feel
the
temperature
difference in front
of or back of the
EEV
under
different
conditions.
dip
switch
master
wired
controller must be
set to "0"
Part 2