Outdoor Unit Network Communication Errors - Fujitsu Airstage J-II Service Manual

Small vrf system
Hide thumbs Also See for Airstage J-II:
Table of Contents

Advertisement

Trouble shooting 13
OUTDOOR UNIT Error Method:
Outdoor Unit Network
Communication 1 Error
Detective Actuators:
Outdoor unit Main PCB
Outdoor unit communication PCB
1. Noise, momentary open, voltage drop 2. Indoor unit power off
Forecast of Cause :
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Main PCB defective
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the indoor unit power supply
Main power ON check
Power cable connection and open check
OK
Check Point 3 : Check the communication line connection
Communication line connection, open check
OK
Check Point 4 : Check the Terminal resistor setting
T erminal resistor setting check
OK
Check Point 5 : Check the communication PCB (outdoor unit/indoor unit)
Communication PCB connection check
Communication PCB check
OK
Check Point 6 : Replace Main PCB (outdoor unit / indoor unit)
Change Main PCB and set up the original address.
Indicate or Display:
Outdoor Unit : E. 14. 1
Indoor Unit
: No display
Error Code
: 14
Detective details:
No communication for 180 seconds or more from an indoor unit which
received communication once and no outdoor network communication error 2.
04-23