Trouble shooting 9
INDOOR UNIT Error Method:
Wired Remote Controller
Communication Error
Detective Actuators:
Indoor unit controller PCB circuit
Wired Remote Control
Forecast of Cause : 1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
Check Point 2 : Check Remote and Controller PCB
controller
Check terminal voltage of
Cassette Type
CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type
If DC12V, Remote Control failure (C
If DC0V, Controller PCB failure (Remote is OK) >>> Replace
In case of re-installation is done due to removed connector or incorrect
-
wiring, turn on the power again.
Trouble shooting 9
INDOOR UNIT Error Method:
Wired Remote Controller Token Error
Detective Actuators:
Indoor unit Controller PCB circuit
Wired Remote Control
Forecast of Cause : 1. Terminal connection abnormal 2. Mis-setting 3. Wired Remote Control failure 4. Controller PCB failure
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of Controller PCB Connector. (Power supply for Remote)
Cassette Type
CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote
lIf DC0V, Controller PCB failure (Remote is OK) >>> Replace Conroller PCB
In case of re-installation is done due to removed connector or incorrect
wiring, turn on the power again.
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit
Error Code
Detective details:
Upon receiving the signal more than 1 time from Wired Remote or other Indoor
unit, but the same signal has not been received more than 1 minute.
PCB Connector. (Power supply for Remote)
ontroller
PCB is OK) >>> Replace Remote
Controller
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Outdoor Unit : E.5 U.1, Error LED Continuous Flash.
Remote Controller : 1 2
Detective details:
More than 1 time of Token (Communication between wired remote controllers)
is received, but it was not received more than 1 minute.
04-19
: Operation LED 1 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
: 1 2
CN7 , Other
PCB
Filter LED Continuous Flash.
CN7 , Other
DC
CN17
DC
CN17