Eeprom Access Abnormal (Indoor Unit Main Pcb Error) - Fujitsu Airstage J-II Service Manual

Small vrf system
Hide thumbs Also See for Airstage J-II:
Table of Contents

Advertisement

Trouble shooting 3
INDOOR UNIT Error Method:
EEPROM Access Abnormal
(Indoor Unit Main PCB Error)
Detective Actuators:
Indoor Unit Controller PCB Circuit
Forecast of Cause : 1. Outside cause 2. Defective connection of electric component 3. Controller PCB defective
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
YES
Check Point 2 :
Check Indoor Unit electric components
Check all connectors (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Indicate or Display:
Outdoor Unit : E.5 U.1
Indoor Unit
: Operation LED 3 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Error Code
: 3 2
Detective details:
When 3 continuous failure occurred on read test of EEPROM.
NO
Check Point 1-2 :
Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus
Momentary power failure ----- Check if there is a defective
Noise ----- Check if there is any equipment causing harmonic
04-13
-
in the same circuit.
contact or leak current in the
power supply circuit.
wave near electric line (Neon bulb or electric
equipment that may cause harmonic wave).
Check the complete insulation of grounding.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage j-iis

Table of Contents