Indoor Unit Fan Motor

Check Point : ARXB24LATH (Low Static pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
150°C
Pr
Check Point : ARXB30/ 36LATH (Low Static pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
150°C
Pr
Check Point : ARXB45LATH (Low Static pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
150°C
Pr
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
04-97
Lead wire
Resistance value
White Red
44.8
37.3
Red
Black
Red
Pink
21.3
Pink
Violet
12.9
Violet
Blue
12.9
Lead wire
Resistance value
White Red
47.1
27.4
Red
Black
Red
Pink
8.00
Pink
Violet
8.00
Violet
Blue
8.00
Lead wire
Resistance value
White Red
20.1
Red
Black
13.8
6.50
Red
Pink
Pink
Violet
6.50
Violet
Blue
6.50
8%
8%
8%
8%
8%
at 20°C
8%
8%
8%
8%
8%
at 20°C
8%
8%
8%
8%
8%
at 20°C