Examples Of System Connection - Mitsubishi Electric PURY-P200 Service Handbook

City multi r410a
Table of Contents

Advertisement

[3]

Examples of system connection

1. System using MA remote controller
(1) In the case of single refrigerant system (Automatic address set-up)
L1
OC
✻ 1
00
00
TB7
TB3
TB02
M1M2
S
M1M2
M1M2
✻ 1
M1M2
NO
TB02
00
BS
✻1
BC and BS are found only in the R2 system.
When connected to the BS, indoor-outdoor automatic
address start up function will not be available.
Prohibited items
1. M-NET and MA remote controllers can not be connected to-
gether to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected
to the indoor unit within the same group.
3. When the total number of indoor units exceeds 26 units In-
cluding that above Type 200, a transmission booster is re-
quired.
4. In the case when start/stop input (CN32, CN51, CN41) is used
by indoor group operation, the "Automatic address set-up"
can not be employed. Please refer to 1. (2) " Manual address
set-up."
5. For the connection of LOSSNAY with more than 2 units in a
single refrigerant system, refer to the following "Connection
of 2 LOSSNAY units in refrigerant system."
Control wiring example
L2
Group
BC
TB5
S
M1M2
S
Group
TB5
M1M2
A1 B2
A1 B2
NO
MA
MA
L3
Group
IC
IC
00
00
TB15
TB5
TB15
S
1 2
M1M2
S
A1 B2
A1 B2
A1 B2
NO
MA
RC
L12
Group
IC
IC
00
00
TB15
TB5
TB15
S
1 2
M1M2
S
1 2
A1 B2
A1 B2
MA
MA
a. Indoor/outdoor transmission line
Farthest length (1.25mm
L1 + L2 + L3 + L4
L1 + L2 + L11 + L12 + L13
b. Centralized control transmission line
No connection is required.
c. MA remote controller wiring
Total length (0.3 ~ 1.25mm
m1
200m
m2 + m3
200m
m4 + m5
200m
Note 1. For the connection to the terminal block of compact
remote controller, employ wire with a diameter of 0.75
~ 1.25mm
2
- 21 -
Interlocking with ventilation
L4
LC
00
TB5
1 2
M1M2
S
MA
L13
IC
00
TB5
TB15
M1M2
S
1 2
m3
– Example to use shielded wire –
Allowable length
2
or more)
200m
200m
2
)

Hide quick links: