Mitsubishi Electric PURY-P200 Service Handbook page 103

City multi r410a
Table of Contents

Advertisement

12. BC controller control (CMB-P
(1) SV
A, SV
B, SV
SV
A, SV
B, SV
Mode
Pipe
end connection
SV
A
SV
B
SV
C
(2) SVM1 control
SVM comes on and off depending on the operation mode.
Operation mode
SVM1
✻2: The pressure difference (PS1, P3) is controlled every minute to stay constant.
(3) LEV
control
The opening of LEV
Operation mode
LEV1
LEV2
Type
Type GA only
G, GA
LEV3
Type
LEV3a
GB
✻1: Superheat control
(G,GA:TH12,TH15, GB:TH22,TH25) is controlled every minute to stay constant.
✻2: The pressure difference (PS1, P3) is controlled every minute to stay constant.
✻3: The liquid level detected on the bases of liquid inlet temperature (TH11) is controlled every minute to stay constant.
✻4: It may exceed 110 due to a pressure rise on the liquid side (PS1).
(4) SVM2 control (Type GA only)
Operation mode
SVM2
G, CMB-P
C control
C comes on and off depending on the mode at the pipe end connection.
Cooling
Heating
ON
OFF
OFF
ON
OFF
Cooling only
Cooling main
Pressure difference
ON
control ✻2
(sj) is controlled based on the operation mode.
Cooling only
Heating only
2000
110
Superheat
Pressure difference
control ✻1
control ✻2
Superheat
60
control ✻1
-
Every minute, the amount of superheat calculated on the bases of bypass outlet/inlet temperature
Cooling only
Cooling main
OFF
OFF
- 100 -
GA, CMB-P
GB)
Stop
OFF
ON
OFF
OFF
Heating only
Heating main
OFF
OFF
Cooling main
Heating main
Liquid-level
110
control
✻4
✻3
Pressure difference
control ✻2
Pressure difference
control ✻2
Superheat
60
control ✻1
Heating only
Heating main
Pressure difference
Pressure difference
control ✻2
control ✻2
Defrost
OFF
OFF
OFF
Defrost
Stop
ON
OFF
Defrost
Stop
2000
1200
G:1000
600
G:2000
60
60
Defrost
Stop
OFF
OFF