(4) Pressure sensor
Work procedure
1. Remove the service panel.
1 For the pressure sensors PS1 and PS3, refer to
(1)-1.2.
2. Remove the applied pressure sensor connector from the
control board, and insulate the connector.
1 Liquid-side pressure sensor (CNP1)
2 Intermediate-part pressure sensor (CNP3)
3. Attach a new pressure sensor to the place which is
shown in the figure, and insert the connector to the
control board.
Note) When the gas leaks from the pressure sensor, fix
the leakage, and follow the instructions above if
required.
(5) LEV
Work procedure
1. Remove the service panel.
(Refer to (1)-2. 3.)
2. Replace the applied LEV.
Note) · Secure enough service space in the ceiling for
welding operation, and conduct the work
carefully.
· If required, dismount the unit from the ceiling,
and conduct the work.
TH11
TH16 PS3
LEV2
TH12
TS15
For G-type, there is no SVM2.
TH11
TH16 PS3
LEV2
TH12
TS15
For G-type, there is no SVM2.
- 194 -
Explanatory figure
PS1 LEV3
CMB-1016V-GA
Explanatory figure
PS1 LEV3
CMB-1016V-GA
LEV1
SVM2
SVM1
LEV1
SVM2
SVM1